Free calculator · NFPA 72 · NEC Chapter 9

NAC Voltage Drop Calculator

Check the end-of-line voltage on a notification appliance circuit and find the longest run your wire size can carry. There is no 10% rule: the last appliance just has to see its listed minimum voltage.

Enter the circuit

Panel to the last appliance.
Sum of appliance draws at their settings.
20.4 V = end of battery discharge on 24 V.
From the appliance datasheet.

End-of-line voltage

0.00 V
  • Wire resistance
  • Loop resistance
  • Voltage drop
  • Maximum one-way length

Worst case: full load at the far end. The panel manufacturer's calculation for the installed equipment governs.

How the voltage drop calculation works

Rloop = (Ω/1000 ft) × 2 × one-way length ÷ 1000
Vdrop = I × Rloop
Vend = Vstart − Vdrop ≥ appliance minimum

The circuit goes out and back, so the wire length is twice the one-way distance. Example: 1.5 A over 200 ft of 14 AWG solid (about 3.07 Ω per 1000 ft) is a 1.23 Ω loop and a 1.84 V drop, leaving 18.56 V at the end. That passes a 16 V appliance, even though it's a 9% drop.

Wire resistance used (NEC Chapter 9, Table 8)

SizeSolid (Ω/1000 ft)Stranded (Ω/1000 ft)
18 AWG7.777.95
16 AWG4.894.99
14 AWG3.073.14
12 AWG1.931.98
10 AWG1.211.24

Uncoated copper, DC resistance at 75°C.

Read more: NAC Voltage Drop: There Is No 10% Rule in NFPA 72.

Voltage Drop Questions

Is there a 10% voltage drop rule in NFPA 72?

No. NFPA 72 does not set a flat percentage. The requirement is that every notification appliance receives at least its listed minimum operating voltage under worst-case conditions.

Why start at 20.4 volts instead of 24?

At the end of the required standby period, a nominal 24 V battery supply can be down to about 20.4 V (85 percent). Calculating from 20.4 V checks the circuit when it is weakest, which is when it still has to work.

What minimum voltage should I use?

The listed minimum operating voltage on each appliance's datasheet. Many 24 V regulated notification appliances are listed down to 16 V, but check the actual model.

Is the lumped-load method too conservative?

It assumes the whole circuit load sits at the far end, which is the worst case. If a circuit fails this check, a point-to-point calculation that places each appliance at its real distance may pass. The panel manufacturer's calculation still governs.

More free calculators

This calculator is a planning aid and does not replace a full design review, the manufacturer's calculation, or the requirements of your authority having jurisdiction. Not affiliated with NFPA.